Wire Gauge Converter

Convert AWG to square millimetres, diameter, resistance and an ampacity figure, for copper or aluminium.

The Wire Gauge Converter runs entirely in your browser. The tables ship with the page and your inputs stay on your device.

Check voltage drop

About Wire Gauge Converter

American Wire Gauge is a geometric series rather than a table someone wrote down: each step down in gauge multiplies the diameter by the 39th root of 92, which is why every three gauges roughly doubles the cross-sectional area and every six halves the diameter. That formula is what this converter runs, in both directions, so an AWG number becomes a diameter, a cross-section in square millimetres and kcmil, and a metric cable size finds its closest gauge. Resistance follows from the same geometry, corrected for conductor temperature and for aluminium. Ampacity is the one figure that is not geometry — it comes from the NEC table, and is shown as guidance rather than as a substitute for your local code.

Features

How to use the Wire Gauge Converter

  1. Pick a direction: AWG to metric, or metric to AWG
  2. Choose the gauge or type the cross-section
  3. Set the conductor material and the insulation temperature rating
  4. Read the dimensions, resistance and ampacity, and add a run length for its total resistance

Example

Input

12 AWG copper

Output

2.053 mm diameter · 3.31 mm² · 5.21 Ω/km · 25 A at 75 °C

The metric equivalent sold in Europe would be 2.5 mm², slightly smaller than 12 AWG.

Common errors & troubleshooting

Frequently asked questions

What is 12 AWG in mm²?
3.31 mm², with a conductor diameter of 2.053 mm. The nearest metric cable size sold in Europe is 2.5 mm², which is slightly smaller, or 4 mm² if you need to be sure of matching it.
How many amps can 12 gauge wire carry?
20 A at a 60 °C insulation rating, 25 A at 75 °C and 30 A at 90 °C in the NEC table, before derating. Circuit protection is usually sized to the 60 °C column for general branch circuits.
Why do AWG numbers get smaller as the wire gets thicker?
The number counts drawing operations. Wire is pulled through successively smaller dies, so a higher number means more passes and a thinner conductor — and the very thick sizes ran out of numbers, which is why they are written 0, 00, 000 and 0000.
How much does wire resistance change with temperature?
Copper rises about 0.39 per cent per degree Celsius. A conductor running at 75 °C has roughly 22 per cent more resistance than the same wire at 20, which matters on a long run near its voltage drop limit.
What is kcmil and where is it used?
Thousands of circular mils, an area unit where one circular mil is the area of a circle a thousandth of an inch across. North American codes use it for conductors larger than 4/0, where AWG numbering stops.